网络增强型控制模块
AZBIL Network Instrumentation Modules Model NX-_ _ _
Equipped with Ethernet Modbus™ or TCP communication as a standard feature, these modules enable multi-loop cooperative control and other types of advanced control technology and networking.
Features and Advantages
  • Support for high-capacity communication: Ethernet communication

  • Optimization functions (process simulation, control of temperature difference between zones)

  • More environmentally friendly control (peak power suppression control, optimal start-up control)

  • Controller module

Accuracy: ± 0.1 % FS (model NX-D35), sampling cycle: 100 ms, number of control channels: 4


Specifications and Parameters

Lineup

Name and modelController Module
NX-D15NX-D25NX-D35
Appearance
Image
c15ad3ab03a4b665187bd802d1240309.png
Image
c15ad3ab03a4b665187bd802d1240309.png
Image
c15ad3ab03a4b665187bd802d1240309.png
Control loops42 or 4
Sampling cycle500ms200ms100ms
Accuracy±0.3% FS ±1 digit±0.1% FS ±1 digit
InputThermocouple, resistance temperature detector, DC voltage, DC current
OutputTransistor
Analog current
Analog voltage
Transistor (motor)-
Rated power supply voltage24 VDC
External dimensions (mm)H100×W30×D104
Specifications SheetNetwork Instrumentation Modules Controller Module Model NX-D15/D25/D35
Model No.Smart Device Gateway
NX-SVG
Appearance
Image
1dfdf6604521df30fd4be896237b450d.png
InterfaceEthernet: 2 channels
RS-485: 2 channels (selectable from CPL and Modbus™/RTU)
USB host communication: USB 2.0
Rated power voltage24 V DC
External dimensions (mm)H100 × W45 × D85
Specifications SheetNetwork Instrumentation Modules Smart Device Gateway Model NX-SVG
*A communication gateway that enables data exchange among a wide variety of control devices without the need for programs, making development work smarter.
Name and modelSupervisor Module
NX-S11NX-S12NX-S21
Appearance
Image
d2016983226ea13c3cd7f36af3fcb924.png
Control loops32
FeaturesControl of temperature difference between zonesOptimal start-up controlPeak power suppression control
Rated power supply voltage24 VDC
External dimensions (mm)H100×W30×D85
Specifications SheetNetwork Instrumentation Modules Supervisor Modules Model NX-S11/S12/S21
Name and modelDigital Input ModuleNX-DX1Pulse Input ModuleNX-DX2Digital Output ModuleNX-DY1Digital Output ModuleNX-DY2
Appearance
Image
8d221474f072a6127e68ca630e14e2fa.png
Image
8d221474f072a6127e68ca630e14e2fa.png
Image
8d221474f072a6127e68ca630e14e2fa.png
Image
8d221474f072a6127e68ca630e14e2fa.png
Inputs16-
Outputs-16(sink)16(source)
Rated power supply voltage24 VDC
External dimensions (mm)H100×W30×D104
Specifications SheetNetwork Instrumentation Modules Digital Input Modules Model NX-DX1/DX2Network Instrumentation Modules Digital Output Modules Model NX-DY1/DY2




Name and modelCommunication BoxNX-CB2Communication AdapterNX-CL1/CR1Terminal AdapterNX-TL1/TR1
Appearance
Image
1847b45eb00617e6a27912a4c7a643fd.png
Image
88d141ea0cf93359c9960aeb1c4fefe1.png
Image
88d141ea0cf93359c9960aeb1c4fefe1.png
Ports41
Mounting methodDIN rail
Rated power supply voltage24 VDC-
External dimensions (mm)H100×W30×D85H100×W20×D26.4H100×W20×D36.5
Specifications SheetNetwork Instrumentation Modules Communications Box (Model NX-CB1), Communications Adapter (Model NX-CL1/CR1), Terminal Adapter (Model NX-TL1/TR1)
User's ManualNetwork Instrumentation Module Model NX-CB2 Communication Box User's Manual for Installation